Siemens SINAMICS G120 List Manual page 209

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

r1343
CO: I_max controller frequency output / I_max_ctrl f_outp
Access level: 3
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays the effective frequency limit.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1340
r1344
I_max controller voltage output / I_max_ctrl U_outp
Access level: 3
Can be changed: -
Unit group: 5_1
Min
- [Vrms]
Description:
Displays the amount by which the converter output voltage is reduced.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1340
p1345[0...n]
I_max voltage controller proportional gain / I_max_U_ctrl Kp
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000
Description:
Sets the proportional gain for the I_max voltage controller.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1340
Note:
The controller settings are also used in the current controller of the DC braking (refer to p1232).
p1346[0...n]
I_max voltage controller integral time / I_max_U_ctrl Tn
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [s]
Description:
Sets the integral time for the I_max voltage controller.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1340
Note:
The controller settings are also used in the current controller of the DC braking (refer to p1232).
For p1346 = 0, the following applies:
The integral time of the I_max voltage controller is de-activated.
r1348
CO: U/f control Eco factor actual value / U/f Eco fac act v
Access level: 4
Can be changed: -
Unit group: -
Min
- [%]
Description:
Displays the economic factor determined for optimizing motor consumption.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [Vrms]
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
100000.000
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
50.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6300
Factory setting
- [rpm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6300
Factory setting
- [Vrms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6300, 7017
Factory setting
0.000
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6300, 7017
Factory setting
0.030 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6300, 6301
Factory setting
- [%]
209

Advertisement

Table of Contents
loading

Table of Contents