Siemens SINAMICS G120 List Manual page 301

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Index:
[0] = Milliseconds
[1] = Days
Dependency:
Refer to: r0948, r2109, r2123, r2125, r2130, r2136, r2145, r2146
Note:
When the electronic power supply is switched out, the counter values are saved.
After the drive unit is switched on, the counter continues to run with the last value that was saved.
p2116[0...n]
BI: External alarm 2 / External alarm 2
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for external alarm 2.
Dependency:
Refer to: A07851
Note:
An external alarm is triggered with a 1/0 signal.
p2117[0...n]
BI: External alarm 3 / External alarm 3
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for external alarm 3.
Dependency:
Refer to: A07852
Note:
An external alarm is triggered with a 1/0 signal.
p2118[0...19]
Change message type message number / Chng type msg_no
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Selects faults or alarms for which the message type should be changed.
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2119
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
p2119[0...19]
Change message type type / Change type type
Access level: 3
Can be changed: U, T
Unit group: -
Min
1
Description:
Sets the message type for the selected fault or alarm.
Value:
1:
2:
3:
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Fault (F)
Alarm (A)
No message (N)
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
3
2 Parameters
2.2 List of parameters
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2546
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2546
Factory setting
1
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8050, 8075
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: 8050, 8075
Factory setting
1
301