OFF2 S_src 1
p0844 [C]
(2090.1)
ON / OFF (OFF1) p0840 [C]
OFF2 S_src 2
p0845 [C]
(1)
OFF3 S_src 1
p0848 [C]
(2090.2)
Operation enable p0852 [C]
OFF3 S_src 2
p0849 [C]
RFG enable p1140 [C]
(1)
Continue RFG p1141 [C]
1st acknowledge
p2103 [C]
(2090.7)
Setpoint enable p1142 [C]
2nd acknowledge
p2104 [C]
(722.2)
3rd acknowledge
p2105 [C]
(0)
Pulse generator
Master ctrl by PLC p0854 [C]
Mop raise p1035 [C]
Mop lower p1036 [C]
1
2
Internal control/status words
Control word 1 (r0054)
STW seq_ctrl
r0898
[2501.7]
(2090.0)
r0898
.0
r0898
[2501.7]
r0898.1
r0898
[2501.7]
r0898.2
r0898
[2501.7]
(2090.3)
r0898.3
r0898
[2501.7]
(2090.4)
r0898.4
r0898
[2501.7]
(2090.5)
r0898.5
r0898
[2501.7]
(2090.6)
r0898.6
r2138
[2546.7]
r2138.7
Jog bit 0 p1055 [C]
r0898
[2501.7]
(0)
r0898.8
Jog bit 1 p1056 [C]
r0898
[2501.7]
(0)
r0898.9
r0898
[2501.7]
(2090.10)
r0898.10
Setp inv p1113 [C]
r1198
[2505.7]
(2090.11)
r1198.11
r1198
[2505.7]
(2090.13)
r1198.13
r1198
[2505.7]
(2090.14)
r1198.14
r0836
[8560.7]
r0836.0
3
4
Bit No.
Control word 1 (r0054)
0 = OFF1, Shutdown via ramp, followed by pulse inhibit
0
1 = ON, operating condition (edge-controlled)
1 = OFF2: Electrical stop, pulse inhibit, motor coasts down
1
0 = Operating condition
1 = OFF3: Quick stop
2
0 = Operating condition
3
1 = Operation enable
4
1 = Ramp-function generator enable
5
1 = Continue ramp-function generator
6
1 = Speed setpoint enable
7
1 = Acknowledge fault
8
1 = Jog bit 0
9
1 = Jog bit 1
10
1 = Master ctrl by PLC
11
1 = Directions reversal (setpoint)
12
Reserved
13
1 = Motorized potentiometer raise
14
1 = Motorized potentiometer lower
15
1 = CDS bit 0
5
fp_2512_97_51.vsd
09.12.2015
STW 1
r0054
r0054
Sequence control
Setpoint channel
Sequence control
Sequence control
Setpoint channel
Sequence control
Setpoint channel
Setpoint channel
Setpoint channel
Sequence control
Sequence control
Setpoint channel
Sequence control
Setpoint channel
Bit 10 in STW1 must be set to ensure
that the drive accepts the process
data.
Setpoint channel
Setpoint channel
Setpoint channel
Sequence control
6
7
Function diagram