2 Parameters
2.2 List of parameters
p2180[0...n]
Output load detection delay time / Out_load det t_del
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [ms]
Description:
Sets the delay time for the message "output load not available" (r2197.11 = 1).
Dependency:
Refer to: p2179
p2181[0...n]
Load monitoring response / Load monit resp
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the response when evaluating the load monitoring.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
Dependency:
Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, p2193, r2198, p3230, p3231
Refer to: A07891, A07892, A07893, F07894, F07895, F07896, A07920, A07921, A07922, F07923, F07924, F07925
Note:
The response to the faults F07923 ... F07925 can be set.
This parameter setting has no effect on the generation of fault F07936.
p2181 = 7, 8 can only be combined with p2193 = 4, 5.
p2182[0...n]
Load monitoring speed threshold value 1 / n_thresh 1
Access level: 3
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2183, p2184, p2185, p2186
Refer to: A07926
Note:
In order that the load monitoring can reliably respond, the speed threshold p2182 should always be set lower than the
minimum motor speed to be monitored.
316
Load monitoring disabled
A07920 for torque/speed too low
A07921 for torque/speed too high
A07922 for torque/speed out of tolerance
F07923 for torque/speed too low
F07924 for torque/speed too high
F07925 for torque/speed out of tolerance
Pump/fan load monitoring as alarm
Pump/fan load monitoring as fault
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
8
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned16
Dyn. index: DDS, p0180
Func. diagram: 8022
Factory setting
2000 [ms]
Data type: Integer16
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
0
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
150.00 [rpm]
List Manual (LH11), 01/2016, A5E33839529