2 Parameters
2.2 List of parameters
p1295[0...n]
Vdc_min controller time threshold (U/f) / Vdc_min t_thresh
PM240
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [s]
Description:
Sets the time threshold for the Vdc_min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized.
Prerequisite: p1296 = 1
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Notice:
If a time threshold has been parameterized, the Vdc_max controller should also be activated (p1280 = 3) so that the
drive does not shut down with overvoltage when Vdc_min control is exited (due to the time violation) and in the event
of fault response OFF3. It is also possible to increase the OFF3 ramp-down time p1135.
p1296[0...n]
Vdc_min controller response (kinetic buffering) (U/f / Vdc_min response
PM240
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the response for the Vdc_min controller (kinetic buffering).
Value:
0:
1:
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note:
For p1296 = 1:
The quick stop ramp entered in p1135 must not be equal to zero, to prevent overcurrent shutdown if F07406 is
triggered.
p1297[0...n]
Vdc_min controller speed threshold (U/f) / Vdc_min n_thresh
PM240
Access level: 3
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold for the Vdc-min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized .
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note:
Exiting the Vdc_min control before reaching motor standstill prevents the regenerative braking current from
increasing significantly at low speeds, and after a pulse inhibit, means that the motor coasts down.
r1298
CO: Vdc controller output (U/f) / Vdc_ctrl output
PM230
Access level: 3
PM230_STO
Can be changed: -
PM240
Unit group: 3_1
Min
- [rpm]
Description:
Displays the actual output of the Vdc controller (DC link voltage controller)
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
198
Buffer Vdc until undervoltage, n<p1297 -> F07405
Buff. Vdc until undervolt., n<p1297 -> F07405, t>p1295 -> F07406
Calculated: -
Scaling: -
Unit selection: -
Max
10000.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: p0340 = 1
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0.000 [s]
Data type: Integer16
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
50.00 [rpm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6320
Factory setting
- [rpm]
List Manual (LH11), 01/2016, A5E33839529