2 Parameters
2.2 List of parameters
Note:
For bit 02:
A data set changeover is delayed by the time required for the internal parameter calculation.
For bit 04:
A data set changeover is only carried out when the armature short circuit is not activated.
For bit 05:
A data set changeover is only carried out when pole position identification is not running.
For bit 07:
A data set changeover is only carried out when rotating measurement is not running.
For bit 08:
A data set changeover is only carried out when motor data identification is not running.
r0836.0...1
CO/BO: Command Data Set CDS selected / CDS selected
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the command data set (CDS) selected via the binector input.
Bit field:
Bit
00
01
Dependency:
Refer to: r0050, p0810, p0811
Note:
Command data sets are selected via binector input p0810 and following.
The currently effective command data set is displayed in r0050.
r0837.0...1
CO/BO: Drive Data Set DDS selected / DDS selected
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the drive data set (DDS) selected via the binector input.
Bit field:
Bit
00
01
Dependency:
Refer to: r0051, p0820, p0821
Note:
Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
p0840[0...n]
BI: ON / OFF (OFF1) / ON / OFF (OFF1)
CU240B-2_DP
Access level: 3
CU240E-2_DP
Can be changed: T
CU240E-2 PN
Unit group: -
CU240E-2_PN_F
Min
CU240E-2_DP_F
-
Description:
Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p1055, p1056
126
Signal name
CDS select. bit 0
CDS select. bit 1
Signal name
DDS select. bit 0
DDS select. bit 1
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
ON
ON
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
ON
ON
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8560
Factory setting
-
0 signal
OFF
OFF
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8565
Factory setting
-
0 signal
OFF
OFF
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501, 2512
Factory setting
[0] 2090.0
[1] 0
[2] 0
[3] 0
List Manual (LH11), 01/2016, A5E33839529