2 Parameters
2.2 List of parameters
The estimated moment of inertia is obtained according to the following formula:
Moment of inertia (J) = linear coefficient (p5314) * load torque + constant coefficient (p5315)
Dependency:
The function module "Moment of inertia estimator" (r0108.10) must be activated for the "Moment of inertia precontrol"
function.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p5310, r5311, p5312, p5313, p5314
p5316[0...n]
Moment of inertia precontrol change time moment of inertia / J_prectrl t J
Access level: 3
Can be changed: U, T
Unit group: -
Min
10.00 [ms]
Description:
Sets the change time for the moment of inertia for the moment of inertia precontrol.
Lower values mean that faster changes are possible.
For a higher value, this estimated value is smoothed more significantly.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1400, p1560, p1562
p5350[0...n]
Mot_temp_mod 1/3 boost factor at standstill / Standst boost_fact
Access level: 2
Can be changed: C(3), U, T
Unit group: -
Min
1.0000
Description:
Sets the boost factor for the copper losses at standstill for motor temperature models 1 and 3.
The entered factor is active for speed n = 0 [rpm].
This factor is linearly reduced down to 1 between speeds n = 0 ... 1 [rpm].
The following values are required to calculate the boost factor:
- stall current (I_0, p0318, catalog value)
- thermal stall current (I_th0, catalog value)
The boost factor is calculated as follows:
- p5350 = (I_0 / I_th0)^2
Dependency:
Refer to: p0318, p0612, p5390, p5391
Refer to: F07011, A07012, A07014
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
Temperature model 1 (I2t):
The following applies for firmware version < 4.7 SP6 or p0612.8 = 0:
- parameter p5350 is not active. Internally, a fixed boost factor of 1.333 is used as basis for the calculation.
The following applies from firmware version 4.7 SP6 and p0612.8 = 1:
- parameter p5350 becomes active as described above.
r5389.0...8
CO/BO: Mot_temp status word faults/alarms / Mot_temp ZSW F/A
Access level: 2
Can be changed: -
Unit group: -
Min
-
Description:
Display and BICO output for faults and alarms of the motor temperature monitoring.
Bit field:
Bit
00
01
368
Signal name
Motor temperature measurement fault
active
Motor temperature model fault active
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
5000.00 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
2.0000
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
500.00 [ms]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8017
Factory setting
2.0000
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8016
Factory setting
-
0 signal
No
No
List Manual (LH11), 01/2016, A5E33839529