p0796
CU digital inputs simulation mode setpoint / CU DI simul setp
CU240E-2
Access level: 3
CU240E-2_DP
Can be changed: U, T
CU240E-2 PN
Unit group: -
CU240E-2_F
CU240E-2_PN_F
Min
CU240E-2_DP_F
-
Description:
Sets the setpoint for the input signals in the digital input simulation mode.
Bit field:
Bit
00
01
02
03
04
05
11
12
Dependency:
The simulation of a digital input is selected using p0795.
Refer to: p0795
Note:
This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
T: Terminal
p0797[0...1]
CU analog inputs simulation mode / CU AI sim_mode
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the simulation mode for the analog inputs.
Value:
0:
1:
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency:
The setpoint for the input voltage is specified via p0798.
Refer to: p0798
Note:
This parameter is not saved when data is backed up (p0971).
AI: Analog Input
p0798[0...1]
CU analog inputs simulation mode setpoint / CU AI sim setp
Access level: 3
Can be changed: U, T
Unit group: -
Min
-50.000
Description:
Sets the setpoint for the input value in the simulation mode of the analog inputs.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency:
The simulation of an analog input is selected using p0797.
If AI x is parameterized as a voltage input (p0756), the setpoint is a voltage in V.
If AI x is parameterized as a current input (p0756), the setpoint is a current in mA.
Refer to: p0756, p0797
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Signal name
DI 0 (T. 5)
DI 1 (T. 6)
DI 2 (T. 7)
DI 3 (T. 8)
DI 4 (T. 16)
DI 5 (T. 17)
DI 11 (T. 3, 4) AI 0
DI 12 (T. 10, 11) AI 1
Terminal evaluation for analog input x
Simulation for analog input x
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
High
High
High
High
High
High
High
High
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
2000.000
2 Parameters
2.2 List of parameters
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2201, 2202, 2220,
2221, 2255, 2256
Factory setting
0000 0000 0000 0000 bin
0 signal
Low
Low
Low
Low
Low
Low
Low
Low
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
0.000
FP
-
-
-
-
-
-
-
-
119