Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
r0024
Output frequency smoothed / f_outp smooth
Access level: 3
Can be changed: -
Unit group: -
Min
- [Hz]
Description:
Display of the smoothed output frequency.
Frequency components from the slip compensation (for induction motors) are included.
Dependency:
Refer to: r0066
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output frequency is available smoothed (r0024) and unsmoothed (r0066).
r0025
CO: Output voltage smoothed / U_outp smooth
Access level: 2
Can be changed: -
Unit group: -
Min
- [Vrms]
Description:
Displays the smoothed output voltage of the power unit.
Dependency:
Refer to: r0072
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
r0026
CO: DC link voltage smoothed / Vdc smooth
Access level: 2
Can be changed: -
Unit group: -
Min
- [V]
Description:
Displays the smoothed actual value of the DC link voltage.
Dependency:
Refer to: r0070
Notice:
When measuring a DC link voltage < 200 V, for the Power Module a valid measured value is not supplied. In this
case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the display
parameter.
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0026 sets itself to the lower value of the pulsating DC link voltage.
r0027
CO: Absolute actual current smoothed / I_act abs val smth
Access level: 2
Can be changed: -
Unit group: -
Min
- [Arms]
Description:
Displays the smoothed absolute actual current value.
Dependency:
Refer to: r0068
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: p2000
Unit selection: -
Max
- [Hz]
Calculated: -
Scaling: p2001
Unit selection: -
Max
- [Vrms]
Calculated: -
Scaling: p2001
Unit selection: -
Max
- [V]
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [Arms]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6300, 6799
Factory setting
- [Hz]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5730, 6300, 6799
Factory setting
- [Vrms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6799
Factory setting
- [V]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5730, 6799, 8850,
8950
Factory setting
- [Arms]
31