n_set_fixed Bit 0 p1020 [C]
n_set_fixed Bit 1 p1021 [C]
n_set_fixed Bit 2 p1022 [C]
n_set_fixed Bit 3 p1023 [C]
Inhib neg dir p1110 [C]
Inhib pos dir p1111 [C]
Setp inv p1113 [C]
Mop raise p1035 [C]
Mop lower p1036 [C]
Bypass RFG p1122 [C]
1
2
Internal control/status words
Control word, setpoint channel (r1198)
Bit No.
Control word setpoint channel (r1198)
(0)
0
1 = Fixed setpoint, bit 0
(0)
1 = Fixed setpoint, bit 1
1
(0)
1 = Fixed setpoint, bit 2
2
(0)
3
1 = Fixed setpoint, bit 3
4
Reserved
(0)
5
1 = Inhibit negative direction of rotation
(0)
1 = Inhibit positive direction of rotation
6
Reserved
7
8
Reserved
9
Reserved
10
Reserved
(2090.11)
1 = Setpoint inversion
11
Reserved
12
(2090.13)
1 = Motorized potentiometer, raise
13
(2090.14)
14
1 = Motorized potentiometer, lower
(0)
15
1 = Bypass ramp-function generator
3
4
STW setpoint chan
r1198
r1198
To fixed speed setpoints [3010.2], [3011.2]
r1198.0
To control word 2 [2513.2]
To fixed speed setpoints [3010.2], [3011.2]
r1198.1
To control word 2 [2513.2]
To fixed speed setpoints [3010.2], [3011.2]
r1198.2
To control word 2 [2513.2]
To fixed speed setpoints [3010.2], [3011.2]
r1198.3
To control word 2 [2513.2]
To direction of rotation limiting and
r1198.5
direction of rotation reversal [3040.3]
To direction of rotation limiting and
r1198.6
direction of rotation reversal [3040.5]
To direction of rotation limiting and
r1198.11
direction of rotation reversal [3040.2]
To control word 1 [2512.4]
r1198.13
To the motorized potentiometer [3020.1]
To control word 1 [2512.4]
r1198.14
To the motorized potentiometer [3020.1]
r1198.15
To the ramp-function generator [3060.1], [3070.1]
5
6
Function diagram
fp_2505_97_51.vsd
G120 CU240B/E-2
09.12.2015
V4.7.6
7
8
- 2505 -