2 Parameters
2.2 List of parameters
Note:
The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Once the Control Unit has been booted up for the first time, the motor parameters suitable for the power unit have
been defined, and the control parameters have been calculated accordingly, p0010 is automatically reset to 0.
p0010 = 3 is used for the subsequent commissioning of additional drive data sets (creating data sets: see p0010 =
15).
p0010 = 29, 39, 49: Only for internal Siemens use!
p0010
Drive commissioning parameter filter / Drv comm. par_filt
PM230
Access level: 1
CU240E-2
Can be changed: C(1), T
CU240E-2_DP
Unit group: -
CU240E-2 PN
Min
CU240E-2_F
0
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
1:
2:
3:
5:
15:
29:
30:
39:
49:
Dependency:
Refer to: r3996
Notice:
When the parameter is reset to a value of 0, short-term communication interruptions may occur.
Note:
The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Once the Control Unit has been booted up for the first time, the motor parameters suitable for the power unit have
been defined, and the control parameters have been calculated accordingly, p0010 is automatically reset to 0.
p0010 = 3 is used for the subsequent commissioning of additional drive data sets (creating data sets: see p0010 =
15).
p0010 = 29, 39, 49: Only for internal Siemens use!
p0014
Buffer memory mode / Buf mem mode
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the mode for the buffer memory.
Value:
0:
1:
2:
28
Ready
Quick commissioning
Power unit commissioning
Motor commissioning
Technological application/units
Data sets
Only Siemens int
Parameter reset
Only Siemens int
Only Siemens int
Save in a non-volatile fashion (RAM)
Buffer memory active (non-volatile)
Clear buffer memory
Calculated: -
Scaling: -
Unit selection: -
Max
49
Calculated: -
Scaling: -
Unit selection: -
Max
2
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Integer16
Dyn. index: -
Func. diagram: 2800, 2818
Factory setting
1
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
List Manual (LH11), 01/2016, A5E33839529