2 Parameters
2.2 List of parameters
p0778[0...1]
CU analog outputs characteristic value y1 / CU AO char y1
Access level: 2
Can be changed: U, T
Unit group: -
Min
-20.000 [V]
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p0776
Notice:
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
p0779[0...1]
CU analog outputs characteristic value x2 / CU AO char x2
Access level: 2
Can be changed: U, T
Unit group: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
Refer to: p0776
Notice:
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
p0780[0...1]
CU analog outputs characteristic value y2 / CU AO char y2
Access level: 2
Can be changed: U, T
Unit group: -
Min
-20.000 [V]
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p0776
Notice:
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
116
Calculated: -
Scaling: -
Unit selection: -
Max
20.000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
20.000 [V]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9572
Factory setting
0.000 [V]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9572
Factory setting
100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9572
Factory setting
20.000 [V]
List Manual (LH11), 01/2016, A5E33839529