2 Parameters
2.2 List of parameters
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
r2120
CO: Sum of fault and alarm buffer changes / Sum buffer changed
Access level: 4
Can be changed: -
Unit group: -
Min
-
Description:
Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency:
Refer to: r0944, r2121
r2121
CO: Counter alarm buffer changes / Alrm buff changed
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
This counter is incremented every time the alarm buffer changes.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125
r2122[0...63]
Alarm code / Alarm code
Access level: 2
Can be changed: -
Unit group: -
Min
-
Description:
Displays the number of alarms that have occurred.
Dependency:
Refer to: r2110, r2123, r2124, r2125, r2134, r2145, r2146, r3121, r3123
Notice:
The properties of the alarm buffer should be taken from the corresponding product documentation.
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Alarm buffer structure (general principle):
r2122[0], r2124[0], r2123[0], r2125[0] --> alarm 1 (the oldest)
. . .
r2122[7], r2124[7], r2123[7], r2125[7] --> Alarm 8 (the latest)
When the alarm buffer is full, the alarms that have gone are entered into the alarm history:
r2122[8], r2124[8], r2123[8], r2125[8] --> Alarm 1 (the latest)
. . .
r2122[63], r2124[63], r2123[63], r2125[63] --> alarm 56 (the oldest)
r2123[0...63]
Alarm time received in milliseconds / t_alarm recv ms
Access level: 3
Can be changed: -
Unit group: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the alarm occurred.
Dependency:
Refer to: r2110, r2122, r2124, r2125, r2134, r2145, r2146
Notice:
The time comprises r2145 (days) and r2123 (milliseconds).
302
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [ms]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8065
Factory setting
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8065
Factory setting
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8050, 8065
Factory setting
-
Data type: Unsigned32
Dyn. index: -
Func. diagram: 8050, 8065
Factory setting
- [ms]
List Manual (LH11), 01/2016, A5E33839529