Siemens SINAMICS G120 List Manual page 450

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p9899
SI setpoint checksum SI parameters (processor 2) / SI setp_chksm P2
PM230_STO
Access level: 3
PM240
Can be changed: C(95)
PM250
Unit group: -
PM260
Min
CU240E-2
0000 hex
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Sets the checksum for the Safety Integrated parameters checked using checksums on processor 2 (setpoint
checksum).
Dependency:
Refer to: p9799, r9898
r9925[0...99]
Firmware file incorrect / FW file incorr
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the directory and name of the file whose status as shipped from the factory was identified as impermissible.
Dependency:
Refer to: r9926
Refer to: A01016
Note:
The directory and name of the file is displayed in the ASCII code.
r9926
Firmware check status / FW check status
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the status when the firmware is checked when the system is booted.
0: Firmware not yet checked.
1: Check running.
2: Check successfully completed.
3: Check indicates an error.
Dependency:
Refer to: r9925
Refer to: A01016
p9930[0...8]
System logbook activation / SYSLOG activation
Access level: 4
Can be changed: U, T
Unit group: -
Min
0
Description:
Only for service purposes.
Index:
[0] = System logbook stage (0: Not active)
[1] = COM2/COM1 (0: COM2, 1: COM1)
[2] = Activate file write (0: Not active)
[3] = Display time stamp (0: Not displayed)
[4...7] = Reserved
[8] = System logbook file size (stages, each 10 kB)
450
Calculated: -
Scaling: -
Unit selection: -
Max
FFFF FFFF hex
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
255
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2800
Factory setting
0000 hex
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
0
List Manual (LH11), 01/2016, A5E33839529