2 Parameters
2.1 Overview of parameters
Parameters with a reference to p0340 after "Calculated" depend on the Power Module being
used and the motor. In this case, the values at "Factory setting" do not correspond to the actual
values because these values are calculated during the commissioning. This also applies to the
motor parameters.
Data type
The information on the data type can consist of the following two items (separated by a slash):
• First item
• Second item (for binector or connector input only)
Parameters can have the following data types:
• Integer8
• Integer16
• Integer32
• Unsigned8
• Unsigned16
• Unsigned32
• FloatingPoint32
Depending on the data type of the BICO input parameter (signal sink) and BICO output
parameter (signal source), the following combinations are possible when creating BICO
interconnections:
Table 2-2
Possible combinations of BICO interconnections
BICO output parameter
CO: Unsigned8
CO: Unsigned16
CO: Unsigned32
CO: Integer16
CO: Integer32
CO: FloatingPoint32
Legend:
16
Data type of the parameter.
Data type of the signal source to be interconnected (binector-/connector output).
Unsigned32 /
Integer16
x
x
x
x
x
x
x :
BICO interconnection permitted
–:
BICO interconnection not permitted
rxxxx:
BICO interconnection is only permitted for the specified CO parameters
I8
8-bit integer number
I16
16-bit integer number
I32
32-bit integer number
U8
8 bits without sign
U16
16 bits without sign
U32
32 bits without sign
Float
32-bit floating point number
BICO input parameter
CI parameter
Unsigned32 /
Integer32
x
x
x
x
x
x
Unsigned32 /
FloatingPoint32
r2050
r2060
x
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529