2 Parameters
2.2 List of parameters
Note:
Value range:
0 - 242: Byte offset
65535: Not assigned
r2077[0...15]
PROFIBUS diagnostics peer-to-peer data transfer addresses / PB diag peer addr
CU240B-2_DP
Access level: 3
CU240E-2_DP
Can be changed: -
CU240E-2 PN
Unit group: -
CU240E-2_PN_F
Min
CU240E-2_DP_F
-
Description:
Displays the addresses of the slaves (peers) where peer-to-peer data transfer has been configured via PROFIBUS.
p2079
PROFIdrive PZD telegram selection extended / PZD telegr ext
CU240B-2_DP
Access level: 3
CU240E-2_DP
Can be changed: T
CU240E-2 PN
Unit group: -
CU240E-2_PN_F
Min
CU240E-2_DP_F
1
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value:
1:
20:
350:
352:
353:
354:
999:
Dependency:
Refer to: p0922
Note:
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
288
Standard telegram 1, PZD-2/2
Standard telegram 20, PZD-2/6
SIEMENS telegram 350, PZD-4/4
SIEMENS telegram 352, PZD-6/6
SIEMENS telegram 353, PZD-2/2, PKW-4/4
SIEMENS telegram 354, PZD-6/6, PKW-4/4
Free telegram configuration with BICO
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
999
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
1
List Manual (LH11), 01/2016, A5E33839529