Siemens SINAMICS G120 List Manual page 516

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p20322
NCM 1 run-time group / NCM 1 RTG
Access level: 3
Can be changed: T
Unit group: -
Min
5
Description:
Setting parameter for the run-time group in which the instance NCM 1 of the numeric comparator is to be called.
Value:
5:
6:
9999: Do not calculate
p20323
NCM 1 run sequence / NCM 1 RunSeq
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Setting parameter for the run sequence of instance NCM 1 within the run-time group set in p20322.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20324[0...1]
BI: RSR 2 inputs / RSR 2 inputs
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for set input S and reset input R of instance RSR 2 of the RS flipflop.
Index:
[0] = Set S
[1] = Reset R
r20325
BO: RSR 2 output Q / RSR 2 output Q
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Display parameter for output Q of instance RSR 2 of the RS flipflop
r20326
BO: RSR 2 inverted output QN / RSR 2 inv outp QN
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Display parameter for inverted output QN of instance RSR 2 of the RS flipflop.
516
Run-time group 5
Run-time group 6
Calculated: -
Scaling: -
Unit selection: -
Max
9999
Calculated: -
Scaling: -
Unit selection: -
Max
32000
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Integer16
Dyn. index: -
Func. diagram: 7225
Factory setting
9999
Data type: Unsigned16
Dyn. index: -
Func. diagram: 7225
Factory setting
830
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 7240
Factory setting
0
Data type: Unsigned32
Dyn. index: -
Func. diagram: 7240
Factory setting
-
Data type: Unsigned32
Dyn. index: -
Func. diagram: 7240
Factory setting
-
List Manual (LH11), 01/2016, A5E33839529

Advertisement

Table of Contents
loading

Table of Contents