2 Parameters
2.2 List of parameters
Notice:
For p1145 > 0.0 (RFG tracking) the setpoint is not equal to zero dependent on the selected value. This can therefore
cause the monitoring time in p1227 to be exceeded. In this case, for a driven motor, the pulses are not suppressed.
Note:
Standstill is identified in the following cases:
- the speed actual value falls below the speed threshold in p1226 and the time started after this in p1228 has expired.
- the speed setpoint falls below the speed threshold in p1226 and the time started after this in p1227 has expired.
For p1227 = 300.000 s the following applies:
Monitoring is de-activated.
For p1227 = 0.000 s, the following applies:
With OFF1 or OFF3 and a ramp-down time = 0, the pulses are immediately suppressed and the motor "coasts" down.
Once the Control Unit has been booted up for the first time or if the factory settings have been defined accordingly,
the parameter is defined in accordance with the power unit.
p1228
Pulse suppression delay time / Pulse suppr t_del
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [s]
Description:
Sets the delay time for pulse suppression.
After OFF1 or OFF3, the pulses are canceled, if at least one of the following conditions is fulfilled:
- the speed actual value falls below the threshold in p1226 and the time started after this in p1228 has expired.
- the speed setpoint falls below the threshold in p1226 and the time started after this in p1227 has expired.
Dependency:
Refer to: p1226, p1227
Notice:
When the motor holding brake is activated, pulse cancellation is additionally delayed by the brake closing time
(p1217).
p1230[0...n]
BI: DC braking activation / DC brake act
Access level: 2
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source to activate DC braking.
Dependency:
Refer to: p1231, p1232, p1233, p1234, r1239
Note:
1 signal: DC braking activated.
0 signal: DC braking de-activated.
p1231[0...n]
DC braking configuration / DCBRK config
Access level: 2
Can be changed: U, T
Unit group: -
Min
0
Description:
Setting to activate DC braking.
Value:
0:
4:
5:
14:
Dependency:
Refer to: p0300, p1232, p1233, p1234, r1239
186
No function
DC braking
DC braking for OFF1/OFF3
DC braking below starting speed
Calculated: -
Scaling: -
Unit selection: -
Max
299.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
14
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2701, 8022
Factory setting
0.010 [s]
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 7017
Factory setting
0
Data type: Integer16
Dyn. index: MDS, p0130
Func. diagram: 7014, 7016, 7017
Factory setting
0
List Manual (LH11), 01/2016, A5E33839529