p2140[0...n]
Hysteresis speed 2 / n_hysteresis 2
Access level: 3
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2155, r2197
p2141[0...n]
Speed threshold 1 / n_thresh val 1
Access level: 3
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Dependency:
Refer to: p2142, r2199
p2142[0...n]
Hysteresis speed 1 / n_hysteresis 1
Access level: 3
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the signal "f or n / v comparison value reached or exceeded" (BO:
r2199.1).
Dependency:
Refer to: p2141, r2199
p2144[0...n]
BI: Motor stall monitoring enable (negated) / Mot stall enab neg
Access level: 4
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for the negated enable (0 = enable) of the motor stall monitoring.
Dependency:
Refer to: p2163, p2164, p2166, r2197, r2198
Refer to: F07900
Note:
When interconnecting the enable signal with r2197.7 then the stall signal is suppressed if there is no speed setpoint -
actual value deviation.
r2145[0...63]
Alarm time received in days / t_alarm recv days
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the system runtime in days when the alarm occurred.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125, r2134, r2146
Notice:
The time comprises r2145 (days) and r2123 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
300.00 [rpm]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
300.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
90.00 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
5.00 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
2.00 [rpm]
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 8012
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8065
Factory setting
-