p1138[0...n]
CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
Refer to: p1120
Note:
The ramp-up time is set in p1120.
p1139[0...n]
CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency:
Refer to: p1121
Note:
The ramp-down time is set in p1121.
p1140[0...n]
BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
CU240B-2_DP
Access level: 3
CU240E-2_DP
Can be changed: T
CU240E-2 PN
Unit group: -
CU240E-2_PN_F
Min
CU240E-2_DP_F
-
Description:
Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Ramp-function generator enable.
Dependency:
Refer to: r0054, p1141, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1140[0...n]
BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
CU240B-2
Access level: 3
CU240E-2
Can be changed: T
CU240E-2_F
Unit group: -
Min
-
Description:
Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Ramp-function generator enable.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3060, 3070
Factory setting
1
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3060, 3070
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
[0] 2090.4
[1] 1
[2] 2090.4
[3] 2090.4
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
1
171