Siemens SINAMICS G120 List Manual page 421

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p9661
SI forced checking procedure STO via PM terminals time / FCP_dyn STO PM-T t
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Unit group: -
CU240E-2
Min
CU240E-2_DP
0.00 [h]
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Sets the time interval for monitoring the forced checking procedure and testing the Safety switch-off signal paths for
STO via terminals on the Power Module.
Within the parameterized time, STO must have been de-selected at least once.
Dependency:
Refer to: r9662
Refer to: A01678
Note:
STO: Safe Torque Off
r9662
SI forced checking procedure STO via PM terminals remaining time /
FCP_dyn STO PM-T t
PM240
Access level: 3
PM250
Can be changed: -
PM260
Unit group: -
CU240E-2
Min
CU240E-2_DP
- [h]
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Displays the remaining time for monitoring the forced checking procedure and testing the Safety switch-off signal
paths for STO via terminals on the Power Module.
After the monitoring time set in p9661 has expired, an appropriate alarm is output.
Dependency:
Refer to: p9661
Refer to: A01678
Note:
PM: Power Module
STO: Safe Torque Off
p9670
SI module identification Control Unit / Module ID CU
PM230_STO
Access level: 3
PM240
Can be changed: T
PM250
Unit group: -
PM260
Min
CU240E-2
0
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
CRC via Node Identifier of the Control Unit.
Note:
CU: Control Unit
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: -
Unit selection: -
Max
9000.00 [h]
Calculated: -
Scaling: -
Unit selection: -
Max
- [h]
Calculated: -
Scaling: -
Unit selection: -
Max
4294967295
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
8.00 [h]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [h]
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0
421