2 Parameters
2.2 List of parameters
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
Macros available as standard are described in the technical documentation of the particular product.
r0018
Control Unit firmware version / CU FW version
Access level: 3
Can be changed: -
Unit group: -
Min
0
Description:
Displays the firmware version of the Control Unit.
Dependency:
Refer to: r0197, r0198
Note:
Example:
The value 1010100 should be interpreted as V01.01.01.00.
r0020
Speed setpoint smoothed / n_set smth
Access level: 2
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays the currently smoothed speed setpoint at the input of the speed controller or U/f characteristic (after the
interpolator).
Dependency:
Refer to: r0060
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
r0021
CO: Actual speed smoothed / n_act smooth
Access level: 2
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Display of the calculated and smoothed rotor speed.
Frequency components from the slip compensation (for induction motors) are not included.
Dependency:
Refer to: r0022, r0063
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
r0022
Speed actual value rpm smoothed / n_act rpm smooth
Access level: 3
Can be changed: -
Unit group: -
Min
- [rpm]
Description:
Display of the calculated and smoothed rotor speed.
Frequency components from the slip compensation (for induction motors) are not included.
r0022 is identical to r0021, however, it always has units of rpm and contrary to r0021 cannot be changed over.
Dependency:
Refer to: r0021, r0063
30
Calculated: -
Scaling: -
Unit selection: -
Max
4294967295
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max
- [rpm]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5020, 6799
Factory setting
- [rpm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6799
Factory setting
- [rpm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6799
Factory setting
- [rpm]
List Manual (LH11), 01/2016, A5E33839529