2 Parameters
2.2 List of parameters
p1113[0...n]
BI: Setpoint inversion / Setp inv
CU240B-2_DP
Access level: 3
CU240E-2_DP
Can be changed: T
CU240E-2 PN
Unit group: -
CU240E-2_PN_F
CU240E-2_DP_F
Min
-
Description:
Sets the signal source to invert the setpoint.
Dependency:
Refer to: r1198
Caution:
If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using
p1113 when the technology controller is enabled because this can cause the speed to change suddenly and lead to
positive couplings in the control loop.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1113[0...n]
BI: Setpoint inversion / Setp inv
CU240B-2
Access level: 3
CU240E-2
Can be changed: T
CU240E-2_F
Unit group: -
Min
-
Description:
Sets the signal source to invert the setpoint.
Dependency:
Refer to: r1198
Caution:
If the technology controller is being used as the speed main setpoint (p2251 = 0), do not invert the setpoint using
p1113 when the technology controller is enabled because this can cause the speed to change suddenly and lead to
positive couplings in the control loop.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r1114
CO: Setpoint after the direction limiting / Setp after limit
Access level: 3
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays the speed/velocity setpoint after the changeover and limiting the direction.
p1115
Ramp-function generator selection / RFG selection
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Sets the ramp-function generator type.
Value:
0:
1:
Note:
Another ramp-function generator type can only be selected when the motor is at a standstill.
166
Basic ramp-function generator
Extended ramp-function generator
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
1
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2441, 2442, 2505,
3040
Factory setting
[0] 2090.11
[1] 0
[2] 0
[3] 0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2441, 2442, 2505,
3040
Factory setting
[0] 722.1
[1] 0
[2] 0
[3] 0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 3001, 3040, 3050
Factory setting
- [rpm]
Data type: Integer16
Dyn. index: -
Func. diagram: 3001, 3080
Factory setting
1