Siemens SINAMICS G120 List Manual page 332

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p2258
Technology controller ramp-down time / Tec_ctrl t_ramp-dn
Access level: 2
Can be changed: U, T
Unit group: -
Min
0.00 [s]
Description:
Sets the ramp-down time of the technology controller.
Dependency:
Refer to: p2257
Note:
The ramp-down time is referred to 100 %.
r2260
CO: Technology controller setpoint after ramp-function generator / Tec_ctr set aftRFG
Access level: 2
Can be changed: -
Unit group: 9_1
Min
- [%]
Description:
Sets the setpoint after the ramp-function generator of the technology controller.
p2261
Technology controller setpoint filter time constant / Tec_ctrl set T
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [s]
Description:
Sets the time constant for the setpoint filter (PT1) of the technology controller.
r2262
CO: Technology controller setpoint after filter / Tec_ctr set aftFlt
Access level: 4
Can be changed: -
Unit group: 9_1
Min
- [%]
Description:
Display and connector output for the smoothed setpoint after the setpoint filter (PT1) of the technology controller.
p2263
Technology controller type / Tec_ctrl type
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Sets the type of technology controller.
Value:
0:
1:
p2264[0...n]
CI: Technology controller actual value / Tec_ctrl act val
Access level: 2
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for the actual value of the technology controller.
332
D component in the actual value signal
D component in system deviation
Calculated: -
Scaling: -
Unit selection: -
Max
650.00 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
60.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
1.00 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
0.000 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
Data type: Integer16
Dyn. index: -
Func. diagram: 7958
Factory setting
0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 7958
Factory setting
0
List Manual (LH11), 01/2016, A5E33839529