4 Faults and alarms
4.2 List of faults and alarms
A30049
Power unit: Internal fan faulty
Message class:
Auxiliary unit faulted (20)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The internal fan has failed.
Remedy:
Check the internal fan and replace if necessary.
F30051
Power unit: Motor holding brake short circuit detected
Message class:
External measured value / signal state outside the permissible range (16)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A short-circuit at the motor holding brake terminals has been detected.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the motor holding brake for a short-circuit.
- check the connection and cable for the motor holding brake.
F30052
EEPROM data error
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
EEPROM data error of the power unit module.
Fault value (r0949, interpret decimal):
0, 2, 3, 4:
The EEPROM data read in from the power unit module is inconsistent.
1:
EEPROM data is not compatible to the firmware of the Control Unit.
Remedy:
Replace power unit module.
A30054 (F, N)
Power unit: Undervoltage when opening the brake
Message class:
Supply voltage fault (undervoltage) (3)
Reaction:
NONE
Acknowledge:
NONE
Cause:
When the brake is being opened, it is detected that the power supply voltage is less than 21.4 V
Alarm value (r2124, interpret decimal):
Supply voltage fault [0.1 V].
Example:
Alarm value = 195 --> voltage = 19.5 V
Remedy:
Check the 24 V voltage for stability and value.
F30055
Power unit: Braking chopper overcurrent
Message class:
Braking Module faulted (14)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
An overcurrent condition has occurred in the braking chopper.
Remedy:
- check whether the braking resistor has a short circuit.
- for an external braking resistor, check whether the resistor may have been dimensioned too small.
Note:
The braking chopper is only enabled again at pulse enable after the fault has been acknowledged.
866
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529