p1501[0...n]
BI: Change over between closed-loop speed/torque control / Changeov n/M_ctrl
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for toggling between speed and torque control.
0 signal: Closed-loop speed control
1 signal: Closed-loop torque control
Dependency:
The input connectors to enter the torque are provided using p1511, p1512 and p1513.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1300
Notice:
If the closed-loop torque control is not activated (p1300) and a change is made to closed-loop torque control (p1501),
OFF1 (p0840) does not have its own braking response but pulse suppression when standstill is detected (p1226,
p1227).
Note:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1502[0...n]
BI: Freeze moment of inertia estimator / J_estim freeze
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source to freeze the estimated moment of inertia.
0 signal:
Moment of inertia estimator active
1 signal:
Determined moment of inertia frozen.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1300
Note:
Only active when the "moment of inertia estimator" function module is active (r0108.10 = 1) and p1400.18 =1.
p1503[0...n]
CI: Torque setpoint / M_set
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the torque setpoint for torque control.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
A change is made to closed-loop torque control if, in p1300, closed-loop torque control was selected or if the
selection was made using the changeover source in p1501.
it is also possible to change over in operation using p1501.
r1508
CO: Torque setpoint before supplementary torque / M_set bef. M_suppl
Access level: 2
Can be changed: -
Unit group: 7_1
Min
- [Nm]
Description:
Displays the torque setpoint before entering the supplementary torque.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2003
Unit selection: -
Max
-
Calculated: -
Scaling: p2003
Unit selection: p0505
Max
- [Nm]
2 Parameters
2.2 List of parameters
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2520, 6020
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: -
Factory setting
0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 6020, 6060
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6030, 6060, 6722
Factory setting
- [Nm]
225