Remedy:
- re-commission the safety functions.
- replace the memory card or Control Unit.
For fault value = 129:
- activate the safety commissioning mode (p0010 = 95).
- adapt the PROFIsafe address (p9610).
- start the copy function for SI parameters (p9700 = D0 hex).
- acknowledge data change (p9701 = DC hex).
- exit the safety commissioning mode (p0010 = 0).
- save all parameters (p0971 = 1 or "copy RAM to ROM").
- carry out a POWER ON (switch-off/switch-on) for the Control Unit.
For fault value = 132:
- check the electrical cabinet design and cable routing for EMC compliance
F01658
SI P1 (CU): PROFIsafe telegram number not suitable
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The PROFIsafe telegram number in p60022 is unsuitable for the enabled safety functions.
Possible causes:
- When PROFIsafe is not enabled (p9601.3 = 0), then it is not permissible to select a PROFIsafe telegram in p60022.
- When PROFIsafe is enabled (p9601.3 = 1), then a PROFIsafe telegram must be selected in p60022.
- When the transfer of the F-DIs via PROFIsafe (p9501.30 = 1) is selected, then telegram 900 must be selected in
p60022 (this only applies to Control Units, which support Extended Functions via PROFIsafe (r9771.4 = 1)).
Note:
This fault does not result in a safety stop response.
See also: p9501, p9601, p60022
Remedy:
Select the telegram number that matches the Safety functions that have been enabled.
F01659
SI P1 (CU): Write request for parameter rejected
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The write request for one or several Safety Integrated parameters on processor 1 was rejected.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
1: The Safety Integrated password is not set.
2: A reset of the drive parameters was selected. However, the Safety Integrated parameters were not reset, as
Safety Integrated is presently enabled.
3: The interconnected STO input is in the simulation mode.
10: An attempt was made to enable the STO function although this cannot be supported.
14: An attempt was made to enable the PROFIsafe communications although this cannot be supported.
15: An attempt was made to enable the motion monitoring functions integrated in the drive although these cannot be
supported.
18: An attempt was made to enable the PROFIsafe function for Basic Functions although this cannot be supported.
20: An attempt was made to simultaneously enable both the drive-integrated motion monitoring functions via
integrated F-DI and STO via terminals, even though these cannot be supported at the same time.
21: An attempt was made to enable the Safety Integrated functions although these cannot be supported by the
connected Power Module.
26: At a digital input of the Control Unit used by Safety Integrated, an attempt was made to activate the simulation
mode.
28: An attempt was made to enable the "STO via terminals at the Power Module" function although this cannot be
supported.
See also: p0970, p3900, r9771, r9871
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
4 Faults and alarms
4.2 List of faults and alarms
799