Bit field:
Bit
00
01
02
03
04
09
12
16
Note:
For bit 01:
This bit can be used to execute a control-based ESR.
ESR: Extended Stop and Retract
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
r9724
SI Motion crosswise comparison clock cycle / SI Mtn CDC clk cyc
PM240
Access level: 3
PM250
Can be changed: -
PM260
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
- [ms]
CU240E-2_DP_F
Description:
Displays the crosswise comparison clock cycle.
The value indicates the clock cycle time with which each individual CDC value is compared between the two
monitoring channels.
Note:
CDC: Crosswise Data Comparison
r9725[0...2]
SI Motion diagnostics STOP F / SI Mtn Diag STOP F
PM240
Access level: 3
PM250
Can be changed: -
PM260
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
-
CU240E-2_DP_F
Description:
For index 0:
Displays the message value that resulted in the STOP F on the drive.
Value = 0:
Processor 1 signaled a STOP F.
Value = 1 ... 999:
Number of the incorrect date in the crosswise data comparison between the monitoring channels.
Value >= 1000:
Additional diagnostic values of the drive.
For index 1:
Displays the value from processor 1 that resulted in the STOP F.
For index 2:
Displays the value from processor 2 that resulted in the STOP F.
Index:
[0] = Message value for CDC
[1] = Processor 1 CDC actual value
[2] = Processor 2 CDC actual value
Dependency:
Refer to: C01711
Note:
The significance of the individual message values is described in message C01711.
CDC: Crosswise Data Comparison
For index 1, 2:
When Safety message C01711 with message value >= 1000 occurs, these indices are not supplied with values.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Signal name
Forced checking procedure required
STOP F and then STOP B active
Communication failure
Actual value sensing supplies valid value
Encoderless act val sensing acc to
technique for U/f control
Safe pulse suppression active
Test stop active
SAM/SBR active
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
- [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
0 signal
No
No
No
No
No
No
No
No
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [ms]
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
FP
-
2819
-
2821
-
-
-
2820
427