2 Parameters
2.2 List of parameters
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Recommendation:
If the ground fault test is incorrectly initiated because the motor is not at a complete standstill, then the pulse
cancellation delay time (p1228) should be increased.
Bit field:
Bit
00
01
02
Dependency:
The ground fault test is only possible when the motor is stationary, and is therefore only realized when flying restart is
de-activated (p1200 = 0).
Refer to: p0287
Note:
If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
For bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), it is not repeated.
For bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
r1902
Test pulse evaluation status / Test puls ev stat
Access level: 4
Can be changed: -
Unit group: -
Min
-
Description:
Displays the status of the test pulse evaluation.
Bit field:
Bit
00
01
02
03
04
Note:
If the ground fault test was selected, but not successfully performed, then sufficient current was not be able to be
established during the test pulses.
For bit 04:
A test pulse longer than one sampling time has occurred
p1909[0...n]
Motor data identification control word / MotID STW
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the configuration for the motor data identification.
Bit field:
Bit
00
02
03
05
06
07
262
Signal name
Phase short-circuit test pulse active
Ground fault detection test pulse active
Test pulse at each pulse enable
Signal name
Short-circuit test successfully performed
Phase short-circuit detected
Ground fault test successfully performed
Ground fault detected
Identification pulse width greater than the
minimum pulse width
Signal name
Stator inductance estimate no
measurement
Rotor time constant estimate no
measurement
Leakage inductance estimate no
measurement
Determine Tr and Lsig evaluation in the time
range
Activate vibration damping
De-activate vibration detection
1 signal
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
SINAMICS G120 Control Units CU240B-2/CU240E-2
0 signal
No
No
No
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
No
No
No
No
No
Data type: Unsigned32
Dyn. index: MDS
Func. diagram: -
Factory setting
0000 0000 0000 0000 0000 0000 0000
0000 bin
0 signal
No
No
No
No
No
No
List Manual (LH11), 01/2016, A5E33839529
FP
-
-
-
FP
-
-
-
-
-
FP
-
-
-
-
-
-

Advertisement

Table of Contents
loading

Table of Contents