r0047
Motor data identification and speed controller optimization / MotID and n_opt
Access level: 1
Can be changed: -
Unit group: -
Min
0
Description:
Displays the actual status for the motor data identification (stationary measurement) and the speed controller
optimization (rotating measurement).
Value:
0:
115:
120:
140:
150:
170:
195:
200:
220:
230:
240:
250:
260:
270:
290:
300:
r0050.0...1
CO/BO: Command Data Set CDS effective / CDS effective
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the effective Command Data Set (CDS).
Bit field:
Bit
00
01
Dependency:
Refer to: p0810, p0811, r0836
Note:
The Command Data Set selected using a binector input (e.g. p0810) is displayed using r0836.
r0051.0...1
CO/BO: Drive Data Set DDS effective / DDS effective
Access level: 2
Can be changed: -
Unit group: -
Min
-
Description:
Displays the effective Drive Data Set (DDS).
Bit field:
Bit
00
01
Dependency:
Refer to: p0820, p0821, r0837
Note:
When selecting the motor data identification routine and the rotating measurement, the drive data set changeover is
suppressed.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
No measurement
Measurement q leakage inductance (part 2)
Speed controller optimization (vibration test)
Calculate speed controller setting
Measurement moment of inertia
Measurement magnetizing current and saturation characteristic
Measurement q leakage inductance (part 1)
Rotating measurement selected
identification leakage inductance
Identification rotor time constant
Identification stator inductance
Identification stator inductance LQLD
Identification circuit
Identification stator resistance
Identification valve lockout time
Stationary measurement selected
Signal name
CDS eff bit 0
CDS eff bit 1
Signal name
DDS eff bit 0
DDS eff bit 1
Calculated: -
Scaling: -
Unit selection: -
Max
300
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
ON
ON
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
ON
ON
2 Parameters
2.2 List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8560
Factory setting
-
0 signal
OFF
OFF
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8565
Factory setting
-
0 signal
OFF
OFF