2 Parameters
2.2 List of parameters
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
p2128[0...15]
Faults/alarms trigger selection / F/A trigger sel
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the faults/alarms for which a trigger signal should be generated in r2129.0...15.
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
Refer to: r2129
r2129.0...15
CO/BO: Faults/alarms trigger word / F/A trigger word
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Display and BICO output for the trigger signals of the faults/alarms set in p2128[0...15].
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
Refer to: p2128
Note:
CO: r2129 = 0 --> None of the selected messages has occurred.
CO: r2129 > 0 --> At least one of the selected messages has occurred.
r2130[0...63]
Fault time received in days / t_fault recv days
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the system runtime in days when the fault occurred.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2133, r2136
Notice:
The time comprises r2130 (days) and r0948 (milliseconds).
The value displayed in p2130 refers to 01.01.1970.
304
Signal name
Trigger signal p2128[0]
Trigger signal p2128[1]
Trigger signal p2128[2]
Trigger signal p2128[3]
Trigger signal p2128[4]
Trigger signal p2128[5]
Trigger signal p2128[6]
Trigger signal p2128[7]
Trigger signal p2128[8]
Trigger signal p2128[9]
Trigger signal p2128[10]
Trigger signal p2128[11]
Trigger signal p2128[12]
Trigger signal p2128[13]
Trigger signal p2128[14]
Trigger signal p2128[15]
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8050, 8070
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8070
Factory setting
-
0 signal
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8060
Factory setting
-
List Manual (LH11), 01/2016, A5E33839529