2 Parameters
2.2 List of parameters
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0615 to p5391.
Dependency:
Refer to: r0034, p0612, p0615, r0632, p5390
Refer to: F07011, A07014
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
r5397
Mot_temp_mod 3 ambient temperature image p0613 / AmbTmp image p0613
Access level: 2
Can be changed: -
Unit group: 21_1
Min
- [°C]
Description:
Displays the ambient temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p0613.
Dependency:
Refer to: r0034
Note:
Users cannot see and change parameter p0613 (only Siemens internal).
r5398[0...n]
Mot_temp_mod 3 alarm threshold image p5390 / A thr image p5390
Access level: 2
Can be changed: -
Unit group: 21_1
Min
- [°C]
Description:
Displays the alarm threshold for monitoring the motor temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p5390.
Dependency:
Refer to: p5390
Refer to: F07011, A07012, A07014
Note:
Users cannot see and change parameter p5390 (only Siemens internal).
r5399[0...n]
Mot_temp_mod 3 fault threshold image p5391 / F thr image p5391
Access level: 2
Can be changed: -
Unit group: 21_1
Min
- [°C]
Description:
Sets the fault threshold for monitoring the motor temperature for motor temperature model 3.
Fault F07011 is output after the fault threshold is exceeded.
The parameter value is an image of p5391.
Dependency:
Refer to: p5391
Refer to: F07011, A07012, A07014
Note:
Users cannot see and change parameter p5391 (only Siemens internal).
370
Calculated: -
Scaling: -
Unit selection: p0505
Max
- [°C]
Calculated: -
Scaling: -
Unit selection: p0505
Max
- [°C]
Calculated: -
Scaling: -
Unit selection: p0505
Max
- [°C]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 8019
Factory setting
- [°C]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8019
Factory setting
- [°C]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8019
Factory setting
- [°C]
List Manual (LH11), 01/2016, A5E33839529