2 Parameters
2.2 List of parameters
For bit 04 in addition:
For p1210 = 26, the system waits in this state until the switch-on command is available.
p1215
Motor holding brake configuration / Brake config
PM230
Access level: 2
PM230_STO
Can be changed: T
Unit group: -
Min
0
Description:
Sets the holding brake configuration.
Value:
0:
3:
Dependency:
Refer to: p1216, p1217, p1226, p1227, p1228
Caution:
For the setting p1215 = 0, if a brake is used, it remains closed. If the motor moves, this will destroy the brake.
Notice:
If p1215 was set to 3, then when the pulses are suppressed, the brake is closed even if the motor is still rotating.
Pulse suppression can either be caused by a 0 signal at p0844, p0845 or p0852 or as a result of a fault with OFF2
response. If this is not desirable (e.g. for a flying restart), then the brake can be kept open using a 1 signal at p0855.
Note:
if an external motor holding brake is being used, then p1215 should be set to 3 and r0899.12 should be
interconnected as control signal.
The parameter can only be set to zero when the pulses are inhibited.
p1215
Motor holding brake configuration / Brake config
PM240
Access level: 2
PM250, PM260
Can be changed: T
Unit group: -
Min
0
Description:
Sets the holding brake configuration.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p1216, p1217, p1226, p1227, p1228
Caution:
For the setting p1215 = 0, if a brake is used, it remains closed. If the motor moves, this will destroy the brake.
Notice:
If p1215 was set to 1 or if p1215 was set to 3, then when the pulses are suppressed, the brake is closed even if the
motor is still rotating. Pulse suppression can either be caused by a 0 signal at p0844, p0845 or p0852 or as a result
of a fault with OFF2 response. If this is not desirable (e.g. for a flying restart), then the brake can be kept open using
a 1 signal at p0855.
Note:
If a holding brake integrated in the motor is used, then it is not permissible that p1215 is set to 3.
if an external motor holding brake is being used, then p1215 should be set to 3 and r0899.12 should be
interconnected as control signal.
The parameter can only be set to zero when the pulses are inhibited.
p1216
Motor holding brake opening time / Brake t_open
Access level: 2
Can be changed: U, T
Unit group: -
Min
0 [ms]
Description:
Sets the time to open the motor holding brake.
After the holding brake has been controlled (opened), the speed setpoint remains at zero for this time. After this, the
speed setpoint is enabled.
184
No motor holding brake available
Motor holding brake like sequence control connection via BICO
No motor holding brake available
Motor holding brake acc. to sequence control
Motor holding brake always open
Motor holding brake like sequence control connection via BICO
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Integer16
Dyn. index: -
Func. diagram: 2701
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: 2701
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2701
Factory setting
100 [ms]