2 Parameters
2.2 List of parameters
p9556
SI Motion pulse suppression delay time (processor 1) / SI Mtn IL t_del P1
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
0.00 [ms]
CU240E-2_DP_F
Description:
Sets the delay time for STOP A after STOP B.
Dependency:
Refer to: p9560
Refer to: C01701
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
p9558
SI Motion acceptance test mode time limit (processor 1) / SI Mtn acc t P1
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
5000.00 [ms]
CU240E-2_DP_F
Description:
Sets the maximum time for the acceptance test mode.
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Dependency:
Refer to: C01799
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
p9559
SI Motion forced checking procedure timer (processor 1) / SI Mtn dyn timer
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
0.00 [h]
CU240E-2_DP_F
Description:
Sets the time interval for carrying out the forced checking procedure and testing the safety motion monitoring
functions integrated in the drives.
Within the parameterized time, the safety functions must have been tested at least once (including de-selection of the
"STO" function).
This monitoring time is reset each time the test is carried out.
The signal source to initiate the forced checking procedure is set in p9705.
Dependency:
Refer to: p9705
Refer to: A01697, C01798
Note:
STO: Safe Torque Off
p9560
SI Motion pulse suppression shutdown speed (processor 1) / SI Mtn IL v_sh P1
CU240E-2_F
Access level: 3
CU240E-2_PN_F
Can be changed: C(95)
CU240E-2_DP_F
Unit group: -
Min
10.00 [rpm]
Description:
Sets the shutdown speed for the pulse suppression.
Below this speed "standstill" is assumed and for STOP B / SS1, the pulses are suppressed (by changing to STOP A).
Dependency:
Refer to: p9556
Note:
The shutdown speed has no effect for a value = 0.
SS1: Safe Stop 1
410
Calculated: -
Scaling: -
Unit selection: -
Max
3600000.00 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
100000.00 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
9000.00 [h]
Calculated: -
Scaling: -
Unit selection: -
Max
6000.00 [rpm]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2819
Factory setting
600000.00 [ms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
40000.00 [ms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
8.00 [h]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
10.00 [rpm]
List Manual (LH11), 01/2016, A5E33839529