Siemens SINAMICS G120 List Manual page 435

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Bit field:
Bit
00
02
05
07
11
12
19
Dependency:
Refer to: r9871
Note:
STO: Safe Torque Off
r9771
SI common functions (processor 1) / SI general fct P1
PM240
Access level: 3
PM250
Can be changed: -
PM260
Unit group: -
CU240E-2_PN_F
Min
CU240E-2_DP_F
-
Description:
Displays the supported Safety Integrated monitoring functions.
Processor 1 determines this display.
Bit field:
Bit
00
02
04
05
06
07
11
12
19
Dependency:
Refer to: r9871
Note:
STO: Safe Torque Off
r9772.0...21
CO/BO: SI status (processor 1) / SI status P1
PM230_STO
Access level: 2
CU240E-2
Can be changed: -
CU240E-2_DP
Unit group: -
CU240E-2 PN
Min
CU240E-2_F
-
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Displays the Safety Integrated status on processor 1.
Bit field:
Bit
00
01
09
10
15
16
17
19
20
21
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Signal name
STO supported via terminals
Extended Functions supported (p9501 > 0)
Extended Functions integrated in drive
supported (p9601.2 = 1)
Extended Functions encoderless supported Yes
Extended Functions SDI supported
Extended Functions SSM encoderless
supported
Power Module STO is supported
Signal name
STO supported via terminals
Extended Functions supported (p9501 > 0)
Extended Functions PROFIsafe supported
Extended Functions integrated in drive
supported (p9601.2 = 1)
Basic Functions PROFIsafe supported
Extended Functions encoderless supported Yes
Extended Functions SDI supported
Extended Functions SSM encoderless
supported
Power Module STO is supported
Signal name
STO selected on processor 1
STO active on processor 1
STOP A cannot be acknowledged active
STOP A active
STOP F active
STO cause: Safety comm. mode
STO cause selection via terminal (Basic
Functions)
STO cause actual value missing
STO cause selection PROFIsafe (Basic
Functions)
STO cause selection on the other
monitoring channel
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
0 signal
No
No
No
No
No
No
No
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2804
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2804
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
FP
2804
2804
-
-
-
-
-
FP
2804
2804
-
-
-
-
-
-
-
FP
2810
2810
2802
2802
2802
-
-
-
-
-
435