r0037[0...19]
CO: Power unit temperatures / PU temperatures
Access level: 4
Can be changed: -
Unit group: 21_1
Min
- [°C]
Description:
Display and connector output for the temperature in the power unit.
Index:
[0] = Inverter maximum value
[1] = Depletion layer maximum value
[2] = Rectifier maximum value
[3] = Air intake
[4] = Interior of power unit
[5] = Inverter 1
[6] = Inverter 2
[7...10] = Reserved
[11] = Rectifier 1
[12] = Reserved
[13] = Depletion layer 1
[14] = Depletion layer 2
[15] = Depletion layer 3
[16] = Depletion layer 4
[17] = Depletion layer 5
[18] = Depletion layer 6
[19] = Reserved
Notice:
Only for internal Siemens troubleshooting.
Note:
The value of -200 indicates that there is no measuring signal.
r0037[0]: Maximum value of the inverter temperatures (r0037[5...10]).
r0037[1]: Maximum value of the depletion layer temperatures (r0037[13...18]).
r0037[2]: Maximum value of the rectifier temperatures (r0037[11...12]).
The maximum value is the temperature of the hottest inverter, depletion layer, or rectifier.
r0037[2, 3, 6, 11, 14...18] is only relevant for chassis power units.
In the case of a fault, the particular shutdown threshold depends on the power unit, and cannot be read out.
r0038
Power factor smoothed / Cos phi smooth
Access level: 4
Can be changed: -
Unit group: -
Min
-
Description:
Displays the smoothed actual power factor. This refers to the electrical power of the basic fundamental signals at the
converter output terminals.
Notice:
For infeed units, the following applies:
For active powers < 25 % of the rated power, this does not provide any useful information.
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0039[0...2]
CO: Energy display / Energy displ
Access level: 2
Can be changed: -
Unit group: -
Min
- [kWh]
Description:
Displays the energy values at the output terminals of the power unit.
Index:
[0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: p2006
Unit selection: p0505
Max
- [°C]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [kWh]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 8021
Factory setting
- [°C]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6799, 8850, 8950
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [kWh]
35