2 Parameters
2.2 List of parameters
2.2
List of parameters
Product: SINAMICS G120 CU240, Version: 4707900, Language: eng
Objects: CU240B-2, CU240B-2_DP, CU240E-2, CU240E-2_DP, CU240E-2 PN, CU240E-2_F, CU240E-2_PN_F, CU240E-2_DP_F
r0002
Drive operating display / Drv op_display
Access level: 2
Can be changed: -
Unit group: -
Min
0
Description:
Operating display for the drive.
Value:
0:
10:
12:
13:
14:
15:
16:
17:
18:
19:
21:
22:
31:
35:
41:
42:
43:
44:
45:
46:
70:
200:
Dependency:
Refer to: r0046
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
p0003
Access level / Acc_level
Access level: 1
Can be changed: C, U, T
Unit group: -
Min
3
Description:
Sets the access level to read and write parameters.
Value:
3:
4:
Note:
A higher set access level also includes the lower one.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
26
Operation - everything enabled
Operation - set "enable setpoint" = "1" (p1142)
Operation - RFG frozen, set "RFG start" = "1" (p1141)
Operation - set "enable RFG" = "1" (p1140)
Operation - MotID, excit. running
Operation - open brake (p1215)
Operation - withdraw braking with OFF1 using "ON/OFF1" = "1"
Operation - braking with OFF3 can only be interrupted with OFF2
Operation - brake on fault, remove fault, acknowledge
Operation - DC braking active (p1230, p1231)
Ready for operation - set "Operation enable" = "1" (p0852)
Ready for operation - de-magnetizing running (p0347)
Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
Switching-on inhibited - carry out first commissioning (p0010)
Switching-on inhibited - set "ON/OFF1" = "0" (p0840)
Switching-on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
Switching-on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
Switching-on inhibited - supply STO terminal w/ 24 V (hardware)
Switching-on inhibited - rectify fault, acknowledge fault, STO
Switching-on inhibited - exit commissioning mode (p0010)
Initialization
Wait for booting/partial booting
Expert
Service
Calculated: -
Scaling: -
Unit selection: -
Max
200
Calculated: -
Scaling: -
Unit selection: -
Max
4
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
3
List Manual (LH11), 01/2016, A5E33839529