Remedy:
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
F30665
SI P2: System is defective
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A system defect was detected before the last boot or in the actual one. The system might have been rebooted
(reset).
Fault value (r0949, interpret hexadecimal):
40 hex:
- For a Power Module with "STO via terminals at the Power Module" (STO_A/STO_B), these terminals are active
(DIP switch to "ON"). However, the "STO via terminals at the Power Module" function has not been enabled (p9601.7
= p9801.7 = 0).
200000 hex, 4000yy hex:
- fault in the actual booting/operation.
Additional values:
- defect before the last time that the system booted.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
For fault value = 40 hex:
- de-activate terminals STO_A/STO_B on the Power Module (set both DIP-switches to "OFF") or enable the "STO via
terminals at the Power Module" function.
For fault value = 4000yy hex:
- ensure that the Control Unit is connected to the Power Module.
- deselect the "STO via terminals at the Power Module" function.
A30666 (F)
SI Motion P2: Steady-state (static) 1 signal at the F-DI for safe acknowledgment
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A logical 1 signal is present at the F-DI configured in p10106 for more than 10 seconds.
If, at the F-DI no acknowledgment was performed for safe acknowledgment, then a steady-state logical and 0 signal
must be present. This avoids unintentional safety-relevant acknowledgment (or the "Internal Event Acknowledge"
signal) if a wire breaks or one of the two digital inputs bounces.
Remedy:
Set the fail-safe digital input (F-DI) to a logical 0 signal (p10106).
Note:
F-DI: Failsafe Digital Input
F30680
SI Motion P2: Checksum error safety monitoring functions
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The actual checksum calculated by processor 2 and entered in r9398 over the safety-relevant parameters does not
match the reference checksum saved in p9399 at the last machine acceptance.
Safety-relevant parameters have been changed or a fault is present.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret decimal):
0: Checksum error for SI parameters for motion monitoring.
1: Checksum error for SI parameters for component assignment.