p1611[0...n]
Additional acceleration torque (sensorless) / M_suppl_accel
Access level: 2
Can be changed: U, T
Unit group: -
Min
0.0 [%]
Description:
Enters the dynamic torque setpoint for the low-speed range for sensorless vector control.
This parameter is entered as a percentage referred to the rated motor torque (r0333).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
When accelerating and braking p1611 is added to p1610 and the resulting total torque is converted into an
appropriate current setpoint and controlled.
For pure accelerating torques, it is always favorable to use the torque pre-control of the speed controller (p1496).
r1614
EMF maximum / EMF max
Access level: 4
Can be changed: -
Unit group: 5_1
Min
- [Vrms]
Description:
Displays the actual maximum possible electromotive force (EMF) of the separately-excited synchronous motor.
Dependency:
The value is the basis for the flux setpoint.
The maximum possible EMF depends on the following factors:
- Actual DC link voltage (r0070).
- Maximum modulation depth (p1803).
- Field-generating and torque-generating current setpoint.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
p1616[0...n]
Current setpoint smoothing time / I_set T_smooth
Access level: 3
Can be changed: U, T
Unit group: -
Min
4 [ms]
Description:
Sets the smoothing time for the current setpoint.
The current setpoint is generated from p1610 and p1611.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
This parameter is only effective in the range where current is injected for sensorless vector control.
r1623[0...1]
Field-generating current setpoint (steady-state) / Id_set stationary
Access level: 4
Can be changed: -
Unit group: 6_2
Min
- [Arms]
Description:
Displays the steady-state field generating current setpoint (Id_set).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
For index 1:
Reserved.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
200.0 [%]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [Vrms]
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [Arms]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6700, 6721, 6722,
6726
Factory setting
30.0 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6725
Factory setting
- [Vrms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6721, 6722
Factory setting
40 [ms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6723
Factory setting
- [Arms]
239