p2099[0...1]
CI: Connector-binector converter signal source / Con/bin S_src
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency:
Refer to: r2094, r2095
Note:
From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
p2100[0...19]
Change fault response fault number / Chng resp F_no
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Selects the faults for which the fault response should be changed
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2101
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19]
Change fault response response / Chng resp resp
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the fault response for the selected fault.
Value:
0:
1:
2:
3:
5:
6:
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The fault response can only be changed for faults with the appropriate identification.
Example:
F12345 and fault response = NONE (OFF1, OFF2)
--> The fault response NONE can be changed to OFF1 or OFF2.
For value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
NONE
OFF1
OFF2
OFF3
STOP2
Internal armature short-circuit / DC braking
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
6
2 Parameters
2.2 List of parameters
Data type: U32 / Integer16
Dyn. index: -
Func. diagram: 2468, 9360
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8050, 8075
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: 8050, 8075
Factory setting
0