2 Parameters
2.2 List of parameters
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1530[0...n]
Power limit motoring / P_max mot
Access level: 2
Can be changed: U, T
Unit group: 14_5
Min
0.00 [kW]
Description:
Sets the power limit when motoring.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0500, p1531
Note:
The power limit is limited to 300% of the rated motor power.
p1531[0...n]
Power limit regenerative / P_max gen
Access level: 2
Can be changed: U, T
Unit group: 14_5
Min
-100000.00 [kW]
Description:
Sets the regenerative power limit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: r0206, p0500, p1530
Note:
The power limit is limited to 300% of the rated motor power.
For power units without energy recovery capability, the regenerative power limit is preset to 30 % of the power
r0206[0]. For a braking resistor connected to the DC link (p0219 > 0), the power limit when generating is
automatically adapted.
For power units with energy recovery, the parameter is limited to the negative value of r0206[2].
r1533
Current limit torque-generating total / Iq_max total
Access level: 3
Can be changed: -
Unit group: 6_2
Min
- [Arms]
Description:
Displays the maximum torque/force generating current as a result if all current limits.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
r1536[0...1]
Current limit maximum torque-generating current / Isq_max
Access level: 4
Can be changed: -
Unit group: 6_2
Min
- [Arms]
Description:
Displays the maximum limit for the torque-generating current component.
Index 0 indicates the signal limited by the Vdc controller.
Index:
[0] = Limited
[1] = Unlimited
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
230
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
100000.00 [kW]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
-0.01 [kW]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max
- [Arms]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6640
Factory setting
0.00 [kW]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6640
Factory setting
-0.01 [kW]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6640
Factory setting
- [Arms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6640, 6710
Factory setting
- [Arms]