p8542[0...15]
BI: Active STW1 in the BOP/IOP manual mode / STW1 act OP
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
For the manual mode: Setting of the signal sources for STW1 (control word 1).
Index:
[0] = ON/OFF1
[1] = OC / OFF2
[2] = OC / OFF3
[3] = Operation enable
[4] = Ramp-function generator enable
[5] = Continue ramp-function generator
[6] = Speed setpoint enable
[7] = Acknowledge fault
[8] = Jog bit 0
[9] = Jog bit 1
[10] = Master control by PLC
[11] = Direction reversal (setpoint)
[12] = Enable speed controller
[13] = Motorized potentiometer raise
[14] = Motorized potentiometer lower
[15] = CDS bit 0
p8543
CI: Active speed setpoint in the BOP/IOP manual mode / N_act act OP
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
For the manual mode: Sets the signal source for the speed setpoint.
p8552
IOP speed unit / IOP speed unit
Access level: 3
Can be changed: T
Unit group: -
Min
1
Description:
Sets the unit for displaying and entering speeds.
Value:
1:
2:
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Hz
rpm
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
2
2 Parameters
2.2 List of parameters
Data type: U32 / Binary
Dyn. index: -
Func. diagram: -
Factory setting
[0] 8540.0
[1] 8540.1
[2] 8540.2
[3] 8540.3
[4] 8540.4
[5] 8540.5
[6] 8540.6
[7] 8540.7
[8] 8540.8
[9] 8540.9
[10] 8540.10
[11] 8540.11
[12] 8540.12
[13] 8540.13
[14] 8540.14
[15] 8540.15
Data type: U32 / FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
8541[0]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
2