For parallel circuit configurations, the parameter index is assigned to a power unit.
r0204[0...n]
Power unit hardware properties / PU HW property
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the properties supported by the power unit hardware.
Bit field:
Bit
01
07
08
12
13
14
15
p0205
Power unit application / PU application
PM230
Access level: 1
PM230_STO
Can be changed: C(1, 2)
Unit group: -
Min
0
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
1:
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: r3996
Notice:
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note:
When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application (p0500)
and the control mode (p1300) are pre-assigned according to the selected application. The parameter has no
influence when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
PM230 (SINAMICS G120)
PM240 (SINAMICS G120)
PM250 (SINAMICS G120 / S120)
PM260 (SINAMICS G120)
SINAMICS G120 Px
PM340 (SINAMICS S120)
SINAMICS ET200PRO
PM250D (SINAMICS G120D)
SINAMICS G120C
SINAMICS PMV40
SINAMICS PMV60
SINAMICS PMV80
SINAMICS G110M
SINAMICS G
PM330 (SINAMICS G120)
SINAMICS GM
SINAMICS SM
SINAMICS MC
SINAMICS GL
SINAMICS SL
SINAMICS DCM
Signal name
RFI filter available
F3E regenerative feedback into the line
supply
Internal Braking Module
Safe Brake Control (SBC) supported
Safety Integrated supported
Internal LC output filter
Line voltage
Load duty cycle with high overload for vector drives
Load duty cycle with low overload for vector drives
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
No
Yes
Yes
1-phase
Calculated: -
Scaling: -
Unit selection: -
Max
1
2 Parameters
2.2 List of parameters
Data type: Unsigned32
Dyn. index: PDS
Func. diagram: -
Factory setting
-
0 signal
No
No
No
Yes
No
No
3-phase
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
1
FP
-
-
-
-
-
-
-
53