p20383
PLI 1 run sequence / PLI 1 RunSeq
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Setting parameter for the run sequence of instance PLI 1 within the run-time group set in p20382.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p60022
PROFIsafe telegram selection / Ps telegram_sel
CU240E-2_DP
Access level: 3
CU240E-2 PN
Can be changed: T
Unit group: -
Min
0
Description:
Sets the telegram number for PROFIsafe.
Value:
0:
30:
998:
Note:
For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe
telegram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
p60022
PROFIsafe telegram selection / Ps telegram_sel
CU240E-2_PN_F
Access level: 3
CU240E-2_DP_F
Can be changed: T
Unit group: -
Min
0
Description:
Sets the telegram number for PROFIsafe.
Value:
0:
30:
900:
998:
Note:
For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe
telegram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
p60122
PROFIdrive SIC telegram selection / Pd SIC telegr
CU240E-2_PN_F
Access level: 3
CU240E-2_DP_F
Can be changed: T
Unit group: -
Min
700
Description:
Sets the telegram for the Safety Info Channel (SIC).
The SIC telegram p60122 is attached directly to the PZD telegram p0922/p2079.
Value:
700:
999:
Dependency:
Refer to: p0922, p2071, p2079
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
No PROFIsafe telegram selected
PROFIsafe standard telegram 30, PZD-1/1
Compatibility mode (as for firmware version < 4.6)
No PROFIsafe telegram selected
PROFIsafe standard telegram 30, PZD-1/1
PROFIsafe SIEMENS telegram 900, PZD-2/2
Compatibility mode (as for firmware version < 4.6)
Supplementary telegram 700, PZD-0/3
Free telegram configuration with BICO
Calculated: -
Scaling: -
Unit selection: -
Max
32000
Calculated: -
Scaling: -
Unit selection: -
Max
998
Calculated: -
Scaling: -
Unit selection: -
Max
998
Calculated: -
Scaling: -
Unit selection: -
Max
999
2 Parameters
2.2 List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: 7226
Factory setting
990
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
998
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
998
Data type: Integer16
Dyn. index: -
Func. diagram: 2423
Factory setting
999