4.2 List of faults and alarms
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
See also: p1800 (Pulse frequency setpoint)
F30005
Power unit: Overload I2t
Message class:
Power electronics faulted (5)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit was overloaded (r0036 = 100 %).
- the permissible rated power unit current was exceeded for an inadmissibly long time.
- the permissible load duty cycle was not maintained.
Fault value (r0949, interpret decimal):
I2t [100 % = 16384].
Remedy:
- reduce the continuous load.
- adapt the load duty cycle.
- check the motor and power unit rated currents.
- reduce the current limit (p0640).
- during operation with U/f characteristic: reduce the integral time of the current limiting controller (p1341).
See also: r0036 (Power unit overload I2t), r0206 (Rated power unit power), p0307 (Rated motor power)
F30011
Power unit: Line phase failure in main circuit
Message class:
Network fault (2)
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY
Cause:
At the power unit, the DC link voltage ripple has exceeded the permissible limit value.
Possible causes:
- a line phase has failed.
- the 3 line phases are inadmissibly unsymmetrical.
- the capacitance of the DC link capacitor forms a resonance frequency with the line inductance and the reactor
integrated in the power unit.
- the fuse of a phase of a main circuit has ruptured.
- a motor phase has failed.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the main circuit fuses.
- check whether a single-phase load is distorting the line voltages.
- Detune the resonant frequency with the line inductance by using an upstream line reactor.
- Dampen the resonant frequency with the line inductance by switching over the DC link voltage compensation in the
software (see p1810) – or increase the smoothing (see p1806). However, this can have a negative impact on the
torque ripple at the motor output.
- check the motor feeder cables.
F30012
Power unit: Temperature sensor heat sink wire breakage
Message class:
Power electronics faulted (5)
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The connection to a heat sink temperature sensor in the power unit is interrupted.
Fault value (r0949, interpret hexadecimal):
Bit 0: Module slot (electronics slot)
Bit 1: Air intake
Bit 2: Inverter 1
Bit 3: Inverter 2
Bit 4: Inverter 3
Bit 5: Inverter 4
Bit 6: Inverter 5
Bit 7: Inverter 6
858