Siemens SINAMICS G120 List Manual page 210

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1335
Note:
The value is only determined for operating modes with Economic (p1300 = 4, 7).
p1349[0...n]
U/f mode resonance damping maximum frequency / Uf res_damp f_max
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.00 [Hz]
Description:
Sets the maximum output frequency for resonance damping for U/f control.
Resonance damping is inactive above this output frequency.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1338, p1339
Note:
For p1349 = 0, the changeover limit is automatically set to 95 % of the rated motor frequency - however, to a max. of
45 Hz.
p1350[0...n]
U/f control soft start / U/f soft start
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets whether the voltage is continuously increased during the magnetizing phase (p1350 = 1, On) or whether it jumps
directly to the voltage boost (p1350 = 0, Off).
Value:
0:
1:
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
The settings for this parameter have the following advantages and disadvantages:
0 = off (jump directly to voltage boost)
Advantage: Flux is established quickly -> torque is quickly available
Disadvantage: The motor can move while it is being magnetized
1 = on (voltage is continually established)
Advantage: The motor is unlikely to rotate
Disadvantage: The flux is established slower -> torque is available later
p1351[0...n]
CO: Motor holding brake starting frequency / Brake f_start
Access level: 3
Can be changed: U, T
Unit group: -
Min
-300.00 [%]
Description:
Sets the frequency setting value at the slip compensation output for starting up with motor holding brake.
Dependency:
When setting p1351 > 0, then slip compensation is automatically activated (p1335 = 100 %).
Refer to: p1302, p1352
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
Connected with p1352 a value of 100% corresponds to the motor rated slip (r0330).
210
OFF
ON
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
3000.00 [Hz]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
300.00 [%]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6310
Factory setting
0.00 [Hz]
Data type: Integer16
Dyn. index: DDS, p0180
Func. diagram: 6300
Factory setting
0
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6310
Factory setting
0.00 [%]
List Manual (LH11), 01/2016, A5E33839529

Advertisement

Table of Contents
loading

Table of Contents