2 Parameters
2.2 List of parameters
p9651
SI STO debounce time (processor 1) / SI STO t_debou P1
PM230_STO
Access level: 3
PM240
Can be changed: C(95)
PM250
Unit group: -
PM260
Min
CU240E-2
0.00 [ms]
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Sets the debounce time for the failsafe digital inputs used to control the "STO" function.
The debounce time is rounded to whole milliseconds.
Note:
The debounce time is rounded to whole milliseconds. It specifies the maximum duration of a fault pulse at the fail-
safe digital inputs with no reaction/influence on the selection or deselection of the Safety Basic Functions.
Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
p9659
SI forced checking procedure timer / SI FCP Timer
PM230_STO
Access level: 3
PM240
Can be changed: C(95)
PM250
Unit group: -
PM260
Min
CU240E-2
0.00 [h]
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Sets the time interval for carrying out the forced checking procedure and testing the Safety switch-off signal paths.
Within the parameterized time, STO must have been de-selected at least once. The monitoring time is reset each
time that STO is de-selected.
Dependency:
Refer to: A01699
Note:
STO: Safe Torque Off
r9660
SI forced checking procedure remaining time / SI frc chk remain
PM230_STO
Access level: 3
PM240
Can be changed: -
PM250
Unit group: -
PM260
Min
CU240E-2
- [h]
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Displays the time remaining before dynamization and testing of the safety switch-off signal paths (forced checking
procedure).
Dependency:
Refer to: A01699
420
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
9000.00 [h]
Calculated: -
Scaling: -
Unit selection: -
Max
- [h]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
1.00 [ms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2810
Factory setting
8.00 [h]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [h]
List Manual (LH11), 01/2016, A5E33839529