Dependency:
If p0014 = 1, changes in the same parameter, as well as in following parameters will not be copied to the buffer
memory:
Refer to: p0015, p0040, p0340, p0650, p0802, p0803, p0804, p0952, p0969, p0970, p0971, p0972, p1900, p1910,
p1960, p2111, p3900, p3981, p7759, p7761, p7762, p7763, p7764, p7765, p7766, p7767, p7768, p7769, p7775
Refer to: A01066, A01067
Notice:
For p0014 = 1:
The following applies if a memory card is optionally inserted:
- the data in the buffer memory are not automatically written to the memory card.
- when switching off/switching on, a possibly valid parameter set is loaded from the memory card.
- remedy: manually save the parameters before switching off the Control Unit (e.g.. p0971 = 1).
For p0014 = 2:
- with this delete operation, entries in the buffer memory are lost and cannot be retrieved.
In general:
- after the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
The parameter is not influenced by setting the factory setting.
For p0014 = 0:
Parameter changes are saved in the volatile memory (RAM).
Non-volatile storage from RAM to ROM is carried out in the following cases:
- p0971 = 1
- change from p0014 = 0 to 1
For p0014 = 1:
With this setting, alarm A01066 followed by alarm A01067 can occur if parameters are continually changed via a
fieldbus system.
Parameter changes are entered in the volatile memory (RAM) and also in the non-volatile buffer memory.
In the following cases, the entries in the buffer memory are transferred into the ROM and then the buffer memory is
cleared:
- p0971 = 1
- switch off/switch on the Control Unit
- change from p0014 = 1 to 0
For p0014 = 2:
The procedure to clear the entries in the buffer memory is initiated.
p0014 is automatically set to 0 after the entries have been cleared.
p0015
Macro drive unit / Macro drv unit
CU240B-2_DP
Access level: 1
CU240E-2_DP
Can be changed: C, C(1)
CU240E-2 PN
Unit group: -
CU240E-2_PN_F
Min
CU240E-2_DP_F
0
Description:
Runs the corresponding macro files.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
Macros available as standard are described in the technical documentation of the particular product.
p0015
Macro drive unit / Macro drv unit
CU240B-2
Access level: 1
CU240E-2
Can be changed: C, C(1)
CU240E-2_F
Unit group: -
Min
0
Description:
Runs the corresponding macro files.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: -
Unit selection: -
Max
999999
Calculated: -
Scaling: -
Unit selection: -
Max
999999
2 Parameters
2.2 List of parameters
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
7
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
12
29