Siemens SINAMICS G120 List Manual page 336

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p2290[0...n]
BI: Technology controller limiting enable / Tec_ctrl lim enab
Access level: 2
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source to enable the technology controller output.
The technology controller output is enabled with a 1 signal.
The technology controller output is held with a 0 signal.
p2291
CO: Technology controller maximum limiting / Tec_ctrl max_lim
Access level: 3
Can be changed: U, T
Unit group: -
Min
-200.00 [%]
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2292
CO: Technology controller minimum limiting / Tec_ctrl min_lim
Access level: 3
Can be changed: U, T
Unit group: -
Min
-200.00 [%]
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2293
Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.00 [s]
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
Refer to: p2291, p2292
Note:
The time refers to the set maximum and minimum limits (p2291, p2292).
r2294
CO: Technology controller output signal / Tec_ctrl outp_sig
Access level: 2
Can be changed: -
Unit group: -
Min
- [%]
Description:
Display and connector output for the output signal of the technology controller.
Dependency:
Refer to: p2295
336
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 7958
Factory setting
1
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
0.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
1.00 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
List Manual (LH11), 01/2016, A5E33839529

Advertisement

Table of Contents
loading

Table of Contents