Siemens SINAMICS G120 List Manual page 375

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Dependency:
The number of indices depends on p7763.
Refer to: p7763
Note:
KHP: Know-How Protection
Even if know-how protection is set, parameters in this list can be read and written to.
p7765
KHP configuration / KHP config
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Configuration settings for know-how protection.
For bit 00, 01:
When KHP is activated, this means that the OEM can define whether the parameters and DCC data encrypted on the
memory card should be protected before using on other memory cards/Control Units.
For bit 02:
This means that the OEM can define whether it is possible or not to trace the drive data using the device trace
function although KHP is activated.
Bit field:
Bit
00
01
02
Dependency:
Refer to: p7766, p7767, p7768
Note:
KHP: Know-How Protection
For copy protection, the serial numbers of the memory card and/or Control Unit are checked.
The memory card copy protection and preventing data to be traced are only effective when the know-how protection
has been activated.
For bit 00, 01:
If both bits are inadvertently set to 1 (e.g. at the BOP), then the setting of bit 0 applies.
There is no copy protection if both bits are set to 0.
p7766[0...29]
KHP password input / KHP passw input
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the password for know-how protection.
Example of a password:
123aBc = 49 50 51 97 66 99 dec (ASCII characters)
[0] = character 1 (e.g. 49 dec)
[1] = character 2 (e.g. 50 dec)
...
[5] = character 6 (e.g. 99 dec)
[29] = 0 dec (completes the entry)
Dependency:
Refer to: p7767, p7768
Notice:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
When using the STARTER commissioning software, the password should be entered using the associated dialogs.
The following rules apply when entering the password:
- Password entry must start with p7766[0].
- no gaps are permissible in the password.
- Entering a password is completed when writing to p7766[29] (p7766[29] = 0 for passwords less than 30 characters).
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Signal name
Extended copy protection - linked to the
memory card and CU
Basic copy protection - linked to the
memory card
Permit trace and measuring functions for
diagnostic purposes
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0000 bin
0 signal
No
No
No
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
FP
-
-
-
375